PV-03
PV array · Meyer Burger Glass 390 bifacial · Saflisch
Sun 15° · 217°
Output
716
kW
· 65 %
Energy so far
5,155
kWh
Front / rear irradiance
608 / 131
W/m²
Snow on modules
3
%
· 646 kWh lost
Alarms raised
0
Tilt / azimuth
60° / 174°
Front irradiance
608 W/m²
Rear irradiance
131 W/m²
Bifacial gain
+16.2 %
Snow on modules
3 %
Lost to snow
646 kWh
Last slide-off
10:01
Rated power
1,100 kWp
Output now
716.4 kW
Energy today
5,154 kWh
Lifetime
1,436 MWh
Availability
98.87 %
Runtime
1,353 h
Next service
in 1,269 h
Last seen
13:59:58
Total
120
Normal
117
Underperforming
3
Fault
0
Snow covered
0
Needing attention
R1-08A
Cracked cells
Table 1 · column 8 · lower row
82 % of expected
UnderperformingR3-04A
Bypass diode shorted
Table 3 · column 4 · lower row
69 % of expected
UnderperformingR3-10B
Potential-induced degradation
Table 3 · column 10 · upper row
81 % of expected
UnderperformingTelemetry
Front irradiance
608.00 W/m²
Rear irradiance
131.00 W/m²
Module temperature
14.60 °C
Snow on modules
3.00 %
Wind gust
8.50 m/s
Snow load
2.18 kN/m²
String voltage
1,197.00 V
String current
8.68 A
Ambient
-0.60 °C
No alarms on this asset.